Very Low Speed Dual Cross Coolers

General Information
In VERY LOW SPEED DUAL CROSS COOLERS, capacities are between1875 W - 7975 W.
It has 2 series FDCA, FDCH.

FEATURES and APPLICATION
• Ceiling type unit coolers are specially designed for small, medium and large cold room and frozen storage room applications with a wide range capacity from 0,2 kW to 47,55 kW. Besides, it has 3 different noise levels of standart, medium noise level (M) and low noise level(L).
• 3 different fin spacing as 4-6-8 mm.
• The coil circuits are designed for refrigerants R 404A, R 507, R 22 and R 134A.
• Capacities valid for R 404A.

Compact and highly efficient coils have following features:
• Aluminium fins,
• 3/8" and 1/2"copper tubes
• Inlet and outlet connections are copper,
• Refrigerant distributor,
• Test pressure: 34 bar,
• Maximum operating pressure: 21 bar,
• Delivered under positive pressure,
• Schrader valve,
• Low refrigerant charge required circuit design

CASING
• Robust and all-round powder coated (RAL 9016) galvanized steel casing parts provide decorative, high corrosion resistance and smooth surface finish. Proper for food processing applications.
• Stainless steel casing as optional.
• Hinged/Folding drain tray is standard for all models. This application provides easy cleaning and maintenance.
• Intermediate drain pan prevents air by-pass.
• Side panels are removable as standard for easy maintenance

FANS
• On unit coolers highly efficient EBM, ZIEHL-ABEGG or equivalent brand fans are used. ELCO brand fans for “Q” series coolers.
• Fan properties: 230 V, 50 Hz, 1400 rpm; 150V, 50Hz 1100 rpm; 130V, 50Hz 900 rpm
• Motor protection IP44 and IP 54; Insulation class B and F .
• Recommended working conditions between -30°C, -40°C and +55°C.
• Lubrication-free closed type motors
• Fan guards according to safety standards
• Different kinds of motors available as optional.

DEFROST
Standard electrical defrost system:
• E1 type (Light duty) defrost system suitable for 0°C / +5°C cold room applications. Defrost heaters are applied on heat exchanger coil.
• E2 type (Heavy duty) defrost system suitable for -34°C / 0°C frozen room applications. Defrost heaters are applied on both heat exchanger coil and drain tray.
• Drain line heaters, fan hausing heaters, hot gas defrost system and water defrost system are optional.

ACCESSORIES
• Insulated drainage pan.
• Consoles for wall – mounting of the coolers

» Friterm reserves the right to make modifications in the catalog at any time without prior notice.
» All catalogs are formatted as pdf(Adobe Acrobat). If you do not have the Adobe Acrobat Reader you can get it free by clicking here
» If your internet connection is slow, it is recomended to save the catalogues by right clicking and "Save Target As".